How to solve the emergency problem of medical clea

Date of issue:2020-07-20Reading volume:59
  • 0
  • [Abstract]: when the medical clean door is running, the action of opening or closing the door is too slow, mainly because the setting value of the speed knob of opening or closing the door of the control device is too low; the walking resistance is too large; the belt is loose and the tension is not enough. Then adjust the speed knob of the control device to open or close the door; turn off the power supply and move the door leaf manually to check whether there are obstacles in the moving parts; and adjust the belt tension.

      When the medical clean door is running, the action of opening or closing the door is too slow, mainly because the setting value of the speed knob for opening or closing the door of the control device is too low; the walking resistance is too large; the belt is loose and the tension is not enough. Then adjust the speed knob of the control device to open or close the door; turn off the power supply and move the door leaf manually to check whether there are obstacles in the moving parts; and adjust the belt tension.

      When the medical clean door is running, the door does not move, mainly because of power failure, poor electrical connection, locking or double door interlock mode. Then check the power supply, connector, make it contact well, unlock or wait for another door to close.

      When the medical clean door is running, when the door cannot be closed, there are usually interferences in the sensor detection area; the light receiver on the safety photoelectric sensor is attached with debris, and the optical axis is deviated; the control device is faulty; the set value of rebound force is too low. Therefore, the interferences in the detection area of the sensor can be removed, the sensor is replaced, the light receiver is cleaned, the optical axis is adjusted, and the power is turned off Start several more times, still can't close the door, change the control device, adjust the rebound force.



    Suzhou Yuanda Purification Equipment Factory
    Contact Us
    • Contact:Wei Li
    • Telephone:18115488801
    • Phone:18018191490
    • Fax:0512-65900829
    • Q Q:275888823
    • Email:liwei520067@163.com
    • Address:No. 555, Yupan Road, Weitang Town, Xiangcheng District, Suzhou City,Jiangsu Province
    Scan the QR code

    Scan WeChat

    Copyright© Suzhou Yuanda Purification Equipment FactoryRecord information: technical support:Jingma.com  Aoma system